General
This Outdoor oil immersed type power transformer use for single phase, 34.5kV, 33kV, 20kV, 13.2kV and 11kV phase to neutral power system.
The transformer high quality transformer oil, high quality CRGO core, primary and secondary use pure electrolytic copper, both winding and core have shielding processing.
It can design on pole installation, also can adding lighting arrest on primary side.
Main Technical data
Model |
Rated
Capacity (kVA)
|
Primary
rating (V)
|
Tapping
Range(%)
|
Secondary
Rating (V)
|
Loss(W) | |
No load | Load loss | |||||
D11-3 | 3 |
34500/19920
33000/17321
20000/11547
13200/7620
11000/6350
or others
|
±2×2.5%
Or others
|
120-240
240-480
250-500
Or others
|
12 | 45 |
D11-5 | 5 | 25 | 75 | |||
D11-10 | 10 | 50 | 120 | |||
D11-15 | 15 | 65 | 195 | |||
D11-25 | 25 | 105 | 290 | |||
D11-37.5 | 37.5 | 140 | 360 | |||
D11-50 | 50 | 180 | 500 | |||
D11-75 | 75 | 250 | 650 | |||
D11-100 | 100 | 275 | 850 | |||
D11-167 | 167 | 455 | 1410 | |||
D11-250 | 250 | 650 | 2000 | |||
D11-333 | 333 | 845 | 2500 |
Standards
All UNISUN transformers are in conformity with IEC standards, Transformers in conformity with specific country standards can also be supplied. (IEEE, GB)